When speaking with manufacturers however a common statement is that a fire doors gap of up to 8 mm underneath the door is permissible.
Maximum gap under fire door australia.
Manufacturing information can be found on the fire door metal tag plate located on the hinge side edge of the fire door.
If the gap is too wide it may compromise the door s ability to.
3 4 between door and frame.
Up to 15mm gap is approved.
The australian standard requires all doors that lead into a fire isolated stairwell or corridor must have approved signage permanently fitted to the door at eye level.
Maximum allowable gap between leaf and top of finished floor level is 10mm 3 10mm is recommended.
1 8 for more detailed gap information refer to nfpa 80 section 6 3 1 7 and section.
Nfpa 80 fire doors and other opening protectives.
Only 3mm of clearance must be evident between the custom fire door and the frame at the head and the stiles.
1 8 meeting edges for a pair of doors.
Up to 15mm gap is approved on some doors.
The surveyor s excuse is that it is because my carpet is too thick but as the carpet was already in place i do not know what needs to be done to ensure that the gap is reduced.
Maximum allowable gap between leaf and top of finished floor level is 10mm 3 10mm is recommended note.
In general clearance for those allowed gaps are as follows.
However as soon as the door is closed the other side of the threshold which does not have a thick carpet means there is a 1 2 inch gap at the bottom of the fire door.
Contains information on maximum gap allowances for different types of fire doors.
Ensure the door is not asbestos.
If a door is to work effectively in its normal role the door leaf must be free to move within the frame and in order to achieve this there must be a gap around the perimeter.
If the discussed cut amount is approved by that fire doors manufacture ensure a gap no less than 2 5mm to a maximum gap of 10mm anywhere alone the bottom of the door in the closed position.
Under the bottom of a door.
In the closed position gaps between the door and frame jamb head hinge and lock stiles are not to exceed 3mm door leaf to the door seat rebate to not exceed 5mm average bottom.
Mind the gap fire door seals fire doors play a crucial role in restricting the spread of fire and smoke.
Door leaf to door stop not to exceed 3mm average and maximum shall not be more than 5mm excluding pyropanel euroseal frame applications which require 4mm gaps.
Bs9999 2008 recommends for fire doors with cold smoke control that the threshold gap should be either less than 3mm in height or should be fitted with a threshold seal.